SUBESTACION - MEDIDORES DE RESISTENCIA DE AISLACION

MEGOHMETRO IRM-5000P

MEGOHMETRO IRM-5000P - MEDIDOR DE RESISTENCIA DE AISLACION

El Megóhmetro IRM-5000P de Vanguard Instrument es un medidor de aislación de AT microprocesado. Es robusto y portátil, esto lo hace ideal para utilizar en subestaciones y para aplicaciones industriales.

DESCARGAR ARCHIVOIRM-5000P Datasheet

TYPE Insulation resistance meter
PHYSICAL SPECIFICATIONS 19"W x 7"H x 15"D, (48 cm x 17 cm x 38 cm); Weight: 24lbs (10.9 kg)
INPUT POWER 110 - 120 Vac or 220 - 240 Vac (selectable), 50/60Hz
RESISTANCE READING RANGE (0°C to +30°C) 100 K-ohms - 1 M-ohm ±20%, 1 M-ohm - 1 T-ohm ±5%, 1 T-ohm - 5 T-ohm ±20% , 5kV 100 K-ohms - 1 M-ohm ±20%, 1 M-ohm - 100 G-ohms ±5%, 100 G-ohms - 500 G-ohms ±5%, 500 V 1 M-ohm - 10 G-ohms ±5%, 50 V
TEST VOLTAGES Selectable from 50Vdc - 5 KVdc, in 2 Vdc steps
OUTPUT VOLTAGE ACCURACY (0°C to +30°C) ±2%, ±1v of selected voltage with load resistance greater than 100 Mº
SHORT CIRCUIT CURRENT 2 mA max
CURRENT READING RANGE (0°C to +30°C) 0.03 nA - 2 mA; Accuracy: ±5% ±0.2 nA
CAPACITANCE READING RANGE (0°C to +30°C) 0.01 ºF - 10.0 ºF (Test voltage greater than 100V); Accuracy: ±5% ±0.03 ºF
VOLTAGE READING RANGE (0°C to +30°C) 50 - 1250 Vac (rms) or dc; Accuracy: ±5%, ±1V
CAPACITOR DISCHARGE Less than 2 Sec/ºF, automatic at the end of test
HUM REJECTION 1mA per 1kv of test voltage, 2mA rms maximum
BATTERIES Two 12V, 2.0 Ah sealed lead acid batteries. Battery life: typical 6 hrs, continuous testing. The IRM-5000P can be used while charging.
PRINTER Built-in 2.5-inch wide thermal printer can print test results in both tabulated and graphic formats
COMPUTER INTERFACE One RS-232C port
SAFETY UL Certified (UL 61010A-1), CAN/CSA Certified (C22.2 No. 1010.1-92)
ENVIRONMENT Operating: -10º to 50º C (15º to +122º F); Storage: -30º C to 70º C (-22º to +158º F)
CABLES One 6-foot cable set, one 15-foot cable set, ground cable, power cord, cable bag
OPTIONS Transportation Case
WARRANTY One year on parts and labor
Volver a subestaciones
HOME | INVESTIGACION| LOCALIZACION DE FALLAS | PREGUNTAS FRECUENTES | ARTICULOS TECNICOS | CURSOS | EVENTOS | CONTACTO